NICET ITFAS-Level-1 - Inspection and Testing of Fire Alarm Systems Level I Exam

Page: 2 / 3
Total 85 questions

Inspection records for all systems shall be kept for which length of time?

A.

6 months

B.

5 years

C.

Until AHJ reviews records and 1 year

D.

Until the next test and 1 year

How frequently should control equipment for a fire alarm system that is unmonitored for alarm, supervisory, and trouble signals be visually inspected?

A.

Daily

B.

Weekly

C.

Semiannually

D.

Annually

At which height above the floor is the sound level measured for public and private modeaudible devices?

A.

2.5 feet (0.7 meter)

B.

5.0 feet (1.5 meters)

C.

7.5 feet (2.3 meters)

D.

8.0 feet (2.4 meters)

What is the testing frequency of an engine driven generator?

A.

Weekly

B.

Monthly

C.

Semiannually

D.

Annually

Secondary power shall automatically provide power to a protected premises system within how many seconds after the primary power fails?

A.

10

B.

30

C.

60

D.

90

After 15 years, what should be done with nonrestorable, spot-type heat detectors in lieu of testing?

A.

Replace 2 devices

B.

Replace 5 devices

C.

Replace 15 devices

D.

Replace all devices

Which of the following is the inspection frequency of the candela rating of visible appliances?

A.

Initial acceptance and quarterly

B.

Initial acceptance and semiannually

C.

Initial acceptance and if a malfunction occurs

D.

Initial acceptance and no further inspections

An off-normal signal shall be initiated during which of the following travel distances of the valve control apparatus from its normal position?

A.

1/5

B.

1/4

C.

1/3

D.

1/2

The inspection phase, as opposed to the testing phase, of system control equipment should concentrate on which of the following tasks?

A.

Activation of all initiating devices

B.

Operational reliability only

C.

Proof of signals at monitoring facility

D.

Visual inspection only

Which NFPA standard determines the testing of a carbon monoxide device or system?

A.

12

B.

70

C.

72

D.

101