A new office area located inside a warehouse space is being designed as a light hazard occupancy. This office area

may be protected with

A.

quick-response CMSA sprinklers.

B.

standard-response CMSA sprinklers.

C.

standard-response spray sprinklers.

D.

residential sprinklers.

Using the Hazen-Williams formula, determine the friction loss in 150 ft (45.7 m) of 1 in. (25 mm) black steel schedule

40 pipe, flowing 30 gpm (115 lpm) in a wet system.

A.

27.5 psi (1.89 bar)

B.

41.3 psi (2.93 bar)

C.

52.2 psi (3.6 bar)

D.

57.9 psi (3.99 bar)

For an Ordinary Hazard with a design area of 1,500 ft2 (140 m2), what is the minimum number of standard pendent sprinklers required?

A.

12 sprinklers

B.

14 sprinklers

C.

18 sprinklers

D.

20 sprinklers

What is the maximum distance an underground main can be installed under the building to the riser location without

additional requirements?

A.

2 ft (0.6 m)

B.

5 ft (1.5 m)

C.

10 ft (3 m)

D.

15 ft (4.6 m)

Working plans are required to have the total system volume of the system for

A.

wet systems.

B.

open-head deluge systems.

C.

dry systems.

D.

antifreeze systems.

What standard applies for underground malleable iron threaded fittings of Class 150?

A.

ASME B16.1

B.

ASME B16.3

C.

ASME B16.4

D.

ASME B16.5

How much pressure is lost to friction as 1,200 gpm (4542 L/min) travels through 200 ft (61 m) of 5 in. (130 mm) schedule 40 steel pipe with a C-factor of 120?

A.

28 psi (1.9 bar)

B.

24 psi (1.65 bar)

C.

21 psi (1.45 bar)

D.

19 psi (1.31 bar)

In a dry pipe system protection of an Extra Hazard Group I occupancy, how many remote sprinklers should be

considered to initially open to meet the water delivery time requirements?

A.

1

B.

2

C.

3

D.

4

A device for use in applications requiring special water discharge patterns, directional spray, or other unusual

discharge characteristics, is known as a

A.

nozzie.

B.

water mist nozzle.

C.

special sprinkler.

D.

CMSA sprinkler.

What is the minimum calculated design area for a light hazard sprinkler system protecting an open office space with a

noncombustible acoustic ceiling tile installed 6 in. (150 mm) below the bottom of solid wood joists?

A.

900 ft2 (83.6 m2)

B.

1,500 ft2 (139.35 m2)

C.

1,950 ft2 (181.1 m2)

D.

3,000 ft2 (278.7 m2)