What is the minimum design pressure for control mode specific application (CMSA) protection of a solid piled, Class IlI commodity stored 35 ft (11 m) high in a 40 ft (12 m) building?

A.

16 psi (1.1 bar)

B.

25 psi (1.7 bar)

C.

30 psi (2.1 bar)

D.

50 psi (3.4 bar)

A dairy processing plant containing empty plastic crates to a maximum height of 5 ft (1.5 m) should be classified as

what occupancy type?

A.

Light

B.

Ordinary Group 1

C.

Ordinary Group 2

D.

Extra Hazard

What is the maximum percentage a fire pump's rated pressure is permitted to produce at churn condition?

A.

65 percent

B.

100 percent

C.

120 percent

D.

140 percent

The minimum diameter of a private service main to a hydraulically calculated sprinkler system that also supplies a fire

hydrant is

A.

3 in. (75 mm).

B.

4 in. (100 mm).

C.

6 in. (150 mm).

D.

8 in. (200 mm).

A restaurant service area has an 18 ft (5.5 m) high T-Bar ceiling throughout. Using quick-response sprinklers in a wet

sprinkler system, what is the minimum area and density that should be calculated?

A.

0.10 gpm/900 ft2 (4.1 mm/min over 84 m2)

B.

0.10 gpm/1,080 ft2 (4.1 mm/min over 100.3 m2)

C.

0.15 gpm/900 ft2 (6.1 mm/min over 84 m2)

D.

0.15 gpm/1,080 ft2 (6.1 mm/min over 100.3 m2)

Assuming that the sprinkler is listed for such use, what is the maximum deflector distance for standard spray horizontal sidewall sprinklers from the ceiling under non- and limited-combustible ceilings?

A.

4 in. (100 mm)

B.

6 in. (150 mm)

C.

12 in. (300 mm)

D.

18 in. (450 mm)

An existing sprinkler system in a 25 ft (1.5 m) tall building is found to be designed using K-8.0 (115) high temperature

control mode density/area (CMDA) sprinklers with a design criteria of 0.35 gpm/ft2 (13.3 mm/min) over

2000 ft2 (186 m2). What is the maximum storage height permitted for double-row rack storage with 8 ft (2.4 m) aisles

of a nonencapsulated Class IV commodity?

A.

15.5 ft (4.7 m)

B.

16.5 ft (5.0 m)

C.

18.5 ft (5.6 m)

D.

20.5 ft (6.2 m)

A sprinkler system employing automatic sprinklers that are attached to a piping system that contains air that might or

might not be under pressure, with a supplemental detection system installed in the same areas as the sprinklers, is

known as a:

A.

Dry System

B.

Preaction System

C.

Wet System

D.

Deluge System

Annual testing for a 1,500 gpm (5,677 L/min) at 80 psi (1.4 bar) fire pump supporting an attached sprinkler system

demand of 1,800 gpm (6,813 L/min) at 100 psi (6.9 bar) is being conducted. The flow test of the fire pump must

achieve what minimum flow rate and discharge pressure?

A.

1,500 gpm (5,677 L/min) at 80 psi (1.4 bar)

B.

1,600 gpm (6,056 L/min) at 75 psi (5.1 bar)

C

1,800 gpm (6,813 L/min) at 100 psi (6.9 bar)

C.

2,250 gpm (8,516 L/min) at 65 psi (4.5 bar)

An 8 in. (200 mm) Schedule 40 steel main is to be supported from a trapeze hanger. The trapeze hanger is to span between two joists which are 7.5 ft (2.3 m) apart. What is the minimum size of steel pipe the trapeze member is to be made of?

A.

2.5 in. (65 mm) Schedule 40 steel pipe

B.

3 in. (80 mm) Schedule 40 steel pipe

C.

2.5 in. (65 mm) Schedule 10 steel pipe

D.

3 in. (80 mm) Schedule 10 steel pipe