When used for sprinkler system design, the water flow test shall be conducted no more than how many months prior

to work plan submittal?

A.

3

B.

6

C.

12

D.

18

In a building where the maximum ceiling temperature will be 80°F (26°C), what would be the lowest permissible temperature classification for the sprinklers?

A.

Ordinary

B.

High

C.

Intermediate

D.

Extra high

A fire pump must produce at least what percentage of its rated pressure at the 150% flow condition?

A.

50%

B.

65%

C.

100%

D.

120%

A paddle-type water flow alarm indicator shall be installed only in

A.

dry systems.

B.

wet systems.

C.

deluge systems.

D.

pre-action systems.

A sprinkler system has been installed with 100 sprinklers. What is the minimum number of spare sprinklers to be provided?

A.

3

B.

6

C.

9

D.

12

In areas using HVLS fans, where must the fans be located in regards to sprinkler placement?

A.

Centered approximately between four adjacent sprinklers

B.

Centered approximately between two adjacent sprinklers

C.

As close to sprinklers as possible

D.

No requirement

What piping material is acceptable for the suction and discharge piping pressure maintenance pumps?

A.

Copper tube

B.

Black or galvanized steel piping

C.

Listed CPVC piping

D.

HDPE piping

A owner of a new warehouse wishes to store a Class III product in ordinary cardboard boxes that contain 45 percent

by volume expanded plastic. What is the commodity classification?

A.

Cartoned, Group A, expanded plastic

B.

Cartoned, Class III

C.

Cartoned, Class IV

D.

Cartoned, Group A, unexpanded plastic

What is the minimum temperature rating of ceiling sprinklers in roll paper stored at 15 ft. (4.6 m) or less?

A.

100°F (38°C)

B.

135°F (57°C)

C.

150°F (66℃)

D.

175°F (79℃)

What is the required minimum design density/area for protection of floor stacked, idle wood pallets to a height of

8 ft (2.4 m) under a 30 ft (9.1 m) roof deck using high expansion foam with a K11.2 (160) CMDA sprinkler?

A.

0.225 gpm/ft2 (9.15 mm/min) over 1,250 ft2 (115 m2)

B.

0.225 gpm/ft2 (9.15 mm/min) over 2,500 ft2 (230 m2)

C.

0.45 gpm/ft2 (18.3 mm/min) over 1,250 ft2 (115 m2)

D.

0.45 gpm/ft2 (18.3 mm/min) over 2,500 ft2 (230 m2)